      <i id='Abirdj'><tr id='Abirdj'><dt id='Abirdj'><q id='Abirdj'><span id='Abirdj'><b id='Abirdj'><form id='Abirdj'><ins id='Abirdj'></ins><ul id='Abirdj'></ul><sub id='Abirdj'></sub></form><legend id='Abirdj'></legend><bdo id='Abirdj'><pre id='Abirdj'><center id='Abirdj'></center></pre></bdo></b><th id='Abirdj'></th></span></q></dt></tr></i><div id='Abirdj'><tfoot id='Abirdj'></tfoot><dl id='Abirdj'><fieldset id='Abirdj'></fieldset></dl></div>

          <bdo id='Abirdj'></bdo><ul id='Abirdj'></ul>

        1. 暖通空调杂志社>期刊目次>2019年>第8期

          变负荷工况区域供冷管网冷损失分析*

          Cooling loss of district cooling pipe network under variable load conditions

          石利军 司鹏飞 戎向阳 杨正武
          中国建筑西南设计研究院有限公司

          摘要:

          介绍了区域供冷管网的冷损失计算方法,并对典型项目在不同敷设方式、不同负荷率下的管网冷损失进行了计算。结果表明:直埋敷设方式的管网冷损失最小;设计工况下,二次管网冷损失在总输送冷量中占比较小,可控制在1%以下,其中二级泵造成的冷损失占比可达78%以上,是管网冷损失的主要因素。不同负荷工况下,二级泵与管道冷损失比例变化明显:负荷率为80%时,二级泵造成的冷损失占比为75%左右;负荷率为30%时,二者所占比例接近,各占总冷损失的50%;负荷率为10%时,管道冷损失占比达到70%以上,成为系统冷损失的主要部分。

          关键词:区域供冷,冷损失,二级泵,直埋敷设,地沟敷设

          Abstract:

           Presents the calculation method of cooling loss for district cooling pipe network and calculates the cooling loss of pipe network under different laying ways and load rates for a typical project. The result shows that directly buried pipe network can keep a minimum cooling loss. The cooling loss of the secondary pipe network accounts for a small part of its total transport cooling capacity, which can be controlled less than 1%, and the cooling loss of the secondary pump is the key factor and can account for more than 78% under design condition. Cooling loss rates of secondary pump and pipe change significantly under different load rates. The cooling loss of secondary pump accounts for 75% under 80% load rate, and the cooling loss of pipe and secondary pump each accounts for 50% under 30% load rate. However, the cooling loss of pipe accounts for 70% under 10% load rate, which becomes the main part of system cooling loss.

          Keywords:districtcooling,coolingloss,secondarypump,directburiedpipe,in-ductpipe